ABB · ACS580Fault Code 7081Info
ABB ACS580 — 7081 Control Panel Loss
Occurs when communication between the drive and the control panel (HMI) is lost. Usually due to the panel connection or cable.
Updated: 2026-07-05
Symptoms
- 7081 and stop when panel reference is selected
- Panel screen dark or frozen
- Fault changes when panel is reseated
Probable Causes
- Panel connector loose/oxidized
- Damaged panel cable
- Faulty panel
- Strict panel-loss action setting (par. 49.05)
Checkpoints
- Remove, clean and reseat the panel connector
- Test the panel cable on another drive
- Review the panel-loss action (par. 49.05)
Solution
If the panel is only used for monitoring, setting the panel-loss action to 'warning only' avoids unwanted stops.