Skip to content
ELKAR
Danfoss · VLT FC302Fault Code Alarm 4Warning

Danfoss VLT FC302 — Alarm 4 Mains Phase Loss

Raised when loss or severe imbalance of an input phase is detected. DC-link ripple increases.

Updated: 2026-07-05

Symptoms

  • Alarm 4 under load
  • Increased DC-link ripple
  • More vibration/noise

Probable Causes

  • Blown input fuse
  • Loose/oxidized mains terminal
  • Mains phase imbalance

Checkpoints

  • Measure all three input phases
  • Check fuses and terminals
  • Review mains-imbalance tolerance (par. 14-12)

Solution

If mains is healthy, inspect the input rectifier stage or DC-link capacitors.

Related Products

Related Faults

Facing the same issue?

Send your faulty board to our lab or consult our expert team. Free pre-analysis.

+90 543 855 16 44 · info@elkarotomasyon.com