Mitsubishi Electric · FR-A800Fault Code E.OC1Critical
Mitsubishi FR-A800 — E.OC1 Overcurrent During Acceleration
Occurs when output current exceeds the limit during acceleration. Short accel time or high motor/cable current is typical.
Updated: 2026-07-05
Symptoms
- E.OC1 during acceleration
- Recurs on high-inertia loads
- Occurs with the motor connected
Probable Causes
- Too-short acceleration time (Pr.7)
- Motor cable short
- Excessive torque boost (Pr.0)
Checkpoints
- Increase acceleration time (Pr.7)
- Measure motor cable insulation
- Reduce torque boost (Pr.0)
Solution
If cable/motor are healthy, the output stage (IGBT) or current-sensing circuit is inspected in the lab.
Related Products
Related Faults
Related Topics
Facing the same issue?
Send your faulty board to our lab or consult our expert team. Free pre-analysis.
+90 543 855 16 44 · info@elkarotomasyon.com