Schneider Altivar — OSF Mains Overvoltage

Occurs when the mains (input) voltage exceeds the allowed upper limit. Weak grids or reactive-compensation issues trigger it.

Updated: 2026-07-05

Symptoms

  • OSF at certain hours (low grid load)
  • Occurs when compensation switches in
  • Trip right at power-up

Probable Causes

  • Mains overvoltage
  • Capacitor bank/compensation resonance
  • Wrong voltage-range setting

Checkpoints

  • Measure input voltage at different times
  • Assess the compensation system
  • Verify the drive voltage class

Solution

For persistently high mains, a line choke or supply regulation is needed. If a measurement-circuit fault is suspected, the board is tested.