Siemens · SINAMICS G120Fault Code F30002Warning

Siemens SINAMICS G120 — F30002 DC Link Overvoltage

Occurs when the DC-link voltage exceeds the upper threshold. Usually from fast deceleration and undissipated regenerative energy.

Updated: 2026-07-05

Symptoms

  • F30002 trip on deceleration
  • Recurring fault on high-inertia loads
  • Frequent when supply is high

Probable Causes

  • Too-short deceleration time (p1121)
  • No or faulty brake resistor/chopper
  • Vdc_max controller disabled (p1240)
  • Supply overvoltage

Checkpoints

  • Increase deceleration time (p1121)
  • Enable the Vdc_max controller (p1240)
  • Measure the brake resistor if present
  • Check supply voltage

Solution

First extend p1121 and enable the Vdc_max controller. If stops are frequent/fast, add a brake resistor.