Skip to content
ELKAR
Danfoss · VLT FC302Fault Code Alarm 7Warning

Danfoss VLT FC302 — Alarm 7 DC Link Overvoltage

Occurs when the DC-link voltage exceeds the upper limit. Fast deceleration and regenerative energy are the main causes.

Updated: 2026-07-05

Symptoms

  • Alarm 7 on deceleration
  • Recurs on high-inertia loads
  • Occurs when supply is high

Probable Causes

  • Too-short ramp-down time (par. 3-42)
  • No brake resistor/chopper
  • OVC (overvoltage control) off
  • Supply overvoltage

Checkpoints

  • Increase ramp-down time (par. 3-42)
  • Enable OVC (par. 2-17)
  • Check the brake resistor

Solution

First extend the ramp-down time and enable OVC; frequent stops require a brake resistor.

Related Products

Related Faults

Related Topics

Facing the same issue?

Send your faulty board to our lab or consult our expert team. Free pre-analysis.

+90 543 855 16 44 · info@elkarotomasyon.com